Inspection & Preventative Maintenance

Ensure Reliability and Safety with NFPA 70B-Compliant Electrical Maintenance Services


Why Our Maintenance Services Can Benefit Your Company:

Our maintenance services are designed to provide comprehensive support, ensuring that your electrical systems remain safe, efficient, and compliant with industry standards. By implementing proactive inspections and preventative measures, we help you avoid unexpected downtime, costly repairs, and potential safety hazards. With our dedicated approach, you can focus on your operations while we handle the complexities of electrical system maintenance—ultimately improving your productivity and protecting your bottom line.

What You Will Get:

OSHA’s focus on electrical safety has expanded to include comprehensive preventive maintenance practices, referencing NFPA 70B to ensure equipment is maintained to prevent hazards. Companies without a documented electrical maintenance program risk inspections and citations under OSHA's General Duty Clause. Our NFPA 70B-compliant maintenance services help you stay ahead of enforcement actions and keep your systems safe, reliable, and compliant. Maintain a digital or physical log for all inspections and maintenance tasks. Review maintenance schedules periodically and adjust based on the condition and age of the equipment. Provide a quote to perform corrective actions promptly if issues are detected.


Transformers
  • Frequency: Annual visual inspection; comprehensive testing every 3–5 years.
  • Inspection Tasks:
    • Check for oil leaks and ensure proper oil levels (if applicable).
    • Inspect bushings, connectors, and insulators for signs of cracking or contamination.
    • Measure and record operating temperature.
    • Verify proper grounding.
    • Perform infrared thermography to detect hot spots.
  • Preventative Maintenance:
    • Clean transformer surfaces and cooling fins.
    • Tighten all connections.
    • Replace oil if dielectric tests indicate contamination.
Switchgear and Circuit Breakers
  • Frequency: Quarterly visual checks and annual detailed inspections.
  • Inspection Tasks:
    • Check for wear, corrosion, or dirt buildup.
    • Inspect breaker contact surfaces and mechanisms.
    • Verify alignment and secure connections.
    • Perform insulation resistance testing.
  • Preventative Maintenance:
    • Clean internal compartments and contacts.
    • Lubricate moving parts as recommended by the manufacturer.
    • Test trip units to verify accuracy and functionality.
    • Replace or refurbish damaged components.
Panelboards and Distribution Panels
  • Frequency: Semi-annual inspection.
  • Inspection Tasks:
    • Check for loose connections or overheating.
    • Ensure panel covers and dead fronts are secure.
    • Label circuits accurately and ensure updated one-line diagrams are available.
  • Preventative Maintenance:
    • Tighten all lugs and terminals.
    • Clean dust and debris from enclosures.
    • Replace degraded breakers or fuses.
Electrical Cabling and Wiring
  • Frequency: Annual inspection and after any system upgrade.
  • Inspection Tasks:
    • Check for signs of wear, fraying, or insulation damage.
    • Verify cable trays and conduits are free from obstructions.
    • Perform megger testing to verify insulation integrity.
  • Preventative Maintenance:
    • Re-secure any loose cables.
    • Replace damaged or outdated wiring.
    • Ensure wiring complies with code requirements.
Grounding Systems
  • Frequency: Annual verification of continuity and grounding integrity.
  • Inspection Tasks:
    • Test ground connections and measure resistance.
    • Ensure no corrosion at ground rods and connectors.
    • Verify compliance with NFPA and NEC grounding standards.
  • Preventative Maintenance:
    • Tighten loose connections.
    • Replace corroded clamps or conductors.
    • Replenish or improve grounding electrodes if resistance exceeds acceptable limits.
Protective Relays
  • Frequency: Annually or after a significant system disturbance.
  • Inspection Tasks:
    • Perform visual inspection for external damage.
    • Review trip settings against system requirements.
  • Preventative Maintenance:
    • Perform secondary injection testing to verify response accuracy.
    • Calibrate relay settings as necessary.
Uninterruptible Power Supply (UPS) Systems
  • Frequency: Monthly visual checks and semi-annual load tests.
  • Inspection Tasks:
    • Check battery status, fluid levels (for lead-acid), and terminals for corrosion.
    • Inspect inverter and rectifier modules.
    • Verify output voltages.
  • Preventative Maintenance:
    • Replace batteries nearing end-of-life.
    • Clean connections and remove dust from ventilation.
    • Conduct full-load discharge tests.
Lighting Systems
  • Frequency: Quarterly inspections.
  • Inspection Tasks:
    • Check for burned-out bulbs and flickering.
    • Inspect control systems (timers, motion sensors, dimmers).
    • Verify emergency lighting functionality.
  • Preventative Maintenance:
    • Replace lamps and fixtures as needed.
    • Clean lenses and reflectors.
    • Ensure all emergency exit lights meet code compliance.
Contact Us